Always follow the manufacturer's instructions and local codes. Lock out and tag out before service.
Commercial Rooftop Unit (RTU) Maintenance Checklist
Packaged gas heat / DX cooling preventive maintenance
Site / Facility:
Unit Tag / ID:
Make / Model:
Serial Number:
Date:
Technician:
Visit Type:
1Safety and Lockout
2Filters and Airflow
Filter specifications:Size:Qty:Type:
Airflow & Static Pressure Measurements
Return static:in. w.g.
Supply static:in. w.g.
Total external static (ESP):in. w.g.
Nameplate max ESP:in. w.g.
3Belts, Motors and Bearings
Belt part / size:Condition:
4Electrical
Incoming Supply Voltage (Under Load)
L1 - L2:V
L2 - L3:V
L1 - L3:V
Rated Voltage:V
Phase Voltage Unbalance:% (≤ 2% max)
Control Transformer Secondary:VAC (per manufacturer)
Motor Amp Draw vs. Nameplate RLA / FLA
| Motor / Component | Nameplate Rating | Actual Running Amps (L1 / L2 / L3) |
|---|---|---|
| Supply Blower Motor | FLA | L1: A L2: A L3: A |
| Compressor 1 | RLA | L1: A L2: A L3: A |
| Compressor 2 (if equipped) | RLA | L1: A L2: A L3: A |
| Condenser Fan Motor 1 | FLA | Actual: A |
| Condenser Fan Motor 2 | FLA | Actual: A |
| Combustion Draft Inducer Motor | FLA | Actual: A |
Run / Start Capacitors tested:Measured:µFRated:µF (within the rating printed on the capacitor)
5Refrigeration Circuit
Refrigerant Operating Pressures & Temperatures
| Circuit | Refrigerant | Suction Line | Superheat | Liquid Line | Subcooling |
|---|---|---|---|---|---|
| Circuit 1 | psig Sat: °F Line: °F | °F Target: °F | psig Sat: °F Line: °F | °F Target: °F | |
| Circuit 2 | psig Sat: °F Line: °F | °F Target: °F | psig Sat: °F Line: °F | °F Target: °F |
Need to work out actual superheat and subcooling from these readings? Use our Superheat & Subcooling Calculator.
A2L Units (R-454B / R-32), If Equipped
6Coils and Condensate
7Economizer and Dampers
Minimum ventilation position setpoint:% openCalculated fresh air:CFM
8Gas Heat
Gas Combustion & Temperature Rise Readings
Gas Manifold Pressure:in. w.g.(Rated: in. w.g.)
Flue Gas CO:ppm(Record air-free CO; compare to the manufacturer's limit)
Supply Air Temp:°F
Return Air Temp:°F
Measured Temp Rise:°F(Nameplate: – °F)
9Controls, Thermostat and Sequence Check
Control board error code history:
10Roof Curb and Cabinet
11Notes and Sign-Off
Deficiencies Identified & Corrective Actions Completed:
Parts Replaced / Materials Used:
Overall Unit Operating Status:
Technician (Print):
Technician Signature:
Sign-off Date:
Customer / Facility Rep:
Customer Signature:
Sign-off Date: